Onis Visa Diesel Generators

P155GXHD | 150 kVA - 166 kVA | PERKINS | MJB250MA4


P155GXHD 150 kVA - 166 kVA PERKINS MJB250MA4 Diesel Generator
Get a Quote on a P155GXHD PERKINS Generator
1006TAG2Advanced Engine Data

1006TAG2Advanced Alternator Data

P155GXHD Specifications
General Data
Model P155GXHD
Prime kVA 150 kVA
Prime kW 120,00 kW
Standby kVA 166 kVA
Standby kW 132,80 kW
Power Factor 0.8
Voltage (VAC) 400/230 V
Frequency 50 Hz
Phases Three Phases (with Neutral)
Engine Speed 1500 rpm
Exhaust Model MSR/a 80
Exhaust Quantity 1
Exhaust Quantity 1
Exhaust Diameter 89 mm
Base Model GV100
Battery Capacity 100 Ah
Battery Quantity 1
Battery Voltage 12 V
Flexible Model DN75
Flexible Quantity 1
Flexible Diameter 89 mm
Dimensions, Weight & Tank Capacity
Length 3060 mm
Width 1140 mm
Height 2170 mm
Weight 2110 kg
Tank Capacity 360 l
Noise
Silent Canopy @ 7m (dBA) 68
Engine Data
Brand PERKINS
Model 1006TAG2
Continuous Power 150 kVA
Standby Power 166 kVA
RPM 1500 rpm
Electronic Governor Standard
Cooling Water
Air Intake Turbocharged
Cylinders 6
Cubic Capacity (l) 5,99 l
Precision Class A2
Flywheel Power (kWm) 129,3 kW
BMEP (kPa)
Weight (kg) 586 kg
Antifreeze q.ty: 37,22 l
Oil qty (l) 19 l
Heat to radiation (kW) 89,4 kW
Heat to exhaust (kW) 99,1 kW
Heat to coolant (kW) 14 kW
Exhaust temperature (°C) 580 °C
Cooling air flow (m3/min) 154 ³/min
Combustion air flow (m3/min) 10,1 ³/min
Exhaust gas flow (m3/min) 29,1 ³/min
TA Luft emissions Not available
TA Luft 2000 emissions Not available
EPA emissions Not available
Stage Not available
SAE 3-11½
Fuel Consumption
25% Load N/A
50% Load 20 l/h
75% Load 31 l/h
100% Load 41 l/h
110% Load 45 l/h
Alternator Data
Brand MARELLI
Model MJB250MA4
Contin. Power (H cl.kVA) 165,00 kVA
Contin. Power (H cl.kW) 132,00 kW
Stand by power (kVA) 180,00 kVA
Stand by power (kW) 144,00 kW
AVR Model M16FA655A
IP protection 23
Precision (+/- %) 0,5
Connection Stella Series
Phases Three Phases (with Neutral)
Winding Code M0
Lead No 12
Weight (kg) 530 Kg